AHF Functions
Meeting users' requirements:
- PF=0.99 and THDi < 5%
- Compensation for 2- to 50-order harmonics
- Capacitive and inductive reactive power compensation
- Three-phase unbalance co
- Parameter
Active Harmonic Filter | |
Rated input | 400V/690V(-20%-+15%) |
Power grid frequency | 50Hz/60Hz ( range: ±10%) |
Parallel operation | Unlimited |
Overall efficiency | ≥ 97% |
Power grid structure | 3P3L, 3P4L |
CT | 150/5 ~ 10,000/5 |
Performance indicators | |
Rated capacity | 35A/50A/60A/100A/150A |
Harmonic compensation | Available |
Reactive power compensation | Available |
Unbalance compensation | Available |
Filtering range | 2 to 50 orders |
Filtering degree | Adjustable from 2 to 50 |
Filter performance | THDi< 5% |
Overall response time | < 10ms |
Target power factor | Adjustable from -1 to +1 |
Control algorithms | FFT,Intelligemt, and instantaneous reactive power |
Switching frequency | 20kHz |
Noise level | < 60dB |
Communications and monitoring capabilities | |
Communications ports | RS485,and network port |
Communications protocols | TCP/IPPMBus, Modbus, and TCP/IP |
Module display interface | Touch screen |
PC software | Optional |
Protection functions | over-valtage protection, under-voltage protection, short-circuit protection, inverter bridge inverse protection,over-compensation protection, and so on |
Fault alarm | Available, at most 500 alarm records |
Monitoring | Independent monitoring and centralized monitoring |
Mechanical properties | |
Altitude | 1% up 1500 m. Between 1500 m to 4000 m, according to GB/T3859.2, the power decreases by 1% for every additional 100 m. |
Operating temperature | -10℃ ~ +40℃ |
Relative humidity | 5% to 95%, non-condensing |
Protection class | IP20 (other IP classes are customizable.) |